A9 | A9-30-10, Nofuel, direct replacement contactors for ABB A9-30-10, A-Line series, 3 pole,3 phase, 9Amp, 600 Volt, 2HP @ 240V, 5HP @ 480V, 7.5HP @ 600V, installed with 120VAC coil and 1NO aux contact, AC contactor |
A12 | A12-30-10, Nofuel, direct replacement contactors for ABB A12-30-10, A-Line series, 3 pole, 3 phase, 11Amp, 600 Volt, 3HP @ 240V, 7.5HP @ 480V, 10HP @ 600V, installed with 120VAC coil and 1NO aux contact, AC contactor |
A16 | A16-30-10, Nofuel, direct replacement contactors for ABB A16-30-10, A-Line series, 3 pole, 3 phase, 17Amp, 600 Volt, 5HP @ 240V, 10HP @ 480V, 15HP @ 600V, installed with 120VAC coil and 1NO aux contact, AC contactor |
A26 | A26-30-10, Nofuel, direct replacement contactors for ABB A26-30-10, A-Line series, 3 pole, 3 phase, 28Amp, 600 Volt, 10HP @ 240V, 20HP @ 480V, 25HP @ 600V, installed with 120VAC coil and 1NO aux contact, AC contactor |
A30 | A30-30-10, Nofuel, direct replacement contactors for ABB A30-30-10, A-Line series, 3 pole, 3 phase, 34Amp, 600 Volt, 10HP @ 240V, 25HP @ 480V, 30HP @ 600V, installed with 120VAC coil and 1NO aux contact, AC contactor |
A40 | A40-30-10, Nofuel, contactors, direct replacement contactors for ABB A40-30-10, A-Line series, 3 pole, 3 phase, 42Amp, 600 Volt, 15HP @ 240V, 30HP @ 480V, 40HP @ 600V, installed with 120VAC coil and 1NO aux contact, AC contactor |
A50 | A50-30-11, Nofuel, direct replacement contactors for ABB A50-30-11, A-Line series, 3 pole, 3 phase, 54Amp, 600 Volt, 20HP @ 240V, 40HP @ 480V, 50HP @ 600V, installed with 120VAC coil and 1NO/1NC aux contact, AC contactor |
A63 | A63-30-11, Nofuel, direct replacement contactors for ABB A63-30-11, A-Line series, 3 pole, 3 phase, 65Amp, 600 Volt, 25HP @ 240V, 50HP @ 480V, 60HP @ 600V, installed with 120VAC coil and 1NO/1NC aux contact, AC contactor |
A75 | A75-30-11, Nofuel, direct replacement contactors for ABB A75-30-11, A-Line series, 3 pole, 3 phase, 80Amp, 600 Volt, 30HP @ 240V, 60HP @ 480V, 75HP @ 600V, installed with 120VAC coil and 1NO/1NC aux contact, AC contactor |
A95 | A95-30-11, Nofuel, direct replacement contactors for ABB A95-30-11, A-Line series, 3 pole, 3 phase, 95Amp, 600 Volt, 30HP @ 240V, 60HP @ 480V, 75HP @ 600V, installed with 120VAC coil and 1NO/1NC aux contact, AC contactor |
A110 | A110-30-11, Nofuel, direct replacement contactors for ABB A110-30-11, A-Line series, 3 pole, 3 phase, 110Amp, 600 Volt, 40HP @ 240V, 75HP @ 480V, 100HP @ 600V, installed with 120VAC coil and 1NO/1NC aux contact, AC contactor |
A145 | A145-30-11, Nofuel, direct replacement contactors for ABB A145-30-11, A-Line series, 3 pole, 3 phase, 130Amp, 600 Volt, 50HP @ 240V, 100HP @ 480V, 125HP @ 600V, installed with 120VAC coil and 1NO/1NC aux contact, AC contactor |
A185 | A185-30-11, Nofuel, direct replacement contactors for ABB A185-30-11, A-Line series, 3 pole, 3 phase, 156Amp, 600 Volt, 60HP @ 240V, 125HP @ 480V, 150HP @ 600V, installed with 120VAC coil and 1NO/1NC aux contact, AC contactor |
A210 | A210-30-11, Nofuel, direct replacement contactors for ABB A210-30-11, A-Line series, 3 pole, 3 phase, 192Amp, 600 Volt, 75HP @ 240V, 150HP @ 480V, 200HP @ 600V, installed with 120VAC coil and 1NO/1NC aux contact, AC contactor |
A260 | A260-30-11, Nofuel, direct replacement contactors for ABB A260-30-11, A-Line series, 3 pole, 3 phase, 248Amp, 600 Volt, 100HP @ 240V, 200HP @ 480V, 250HP @ 600V, installed with 120VAC coil and 1NO/1NC aux contact, AC contactor |
A300 | A300-30-11, Nofuel, direct replacement contactors for ABB A300-30-11, A-Line series, 3 pole, 3 phase, 302Amp, 600 Volt, 100HP @ 240V, 250HP @ 480V, 300HP @ 600V, installed with 120VAC coil and 1NO/1NC aux contact, AC contactor |
AC Control supply Model No. |
Standard Part Number |
General use rating 600 V AC |
AC-3 Rated operational power |
3-phase motor rating |
NEMA size | Weight in kg |
Model | Amp | KW@480 | HP@480V | NEMA size | ||
A9 | A9-30-10 | 9 | 4 | 5 | 0 | 0.4 |
A12 | A12-30-10 | 12 | 5.5 | 7.5 | 0 | 0.4 |
A16 | A16-30-10 | 16 | 7.5 | 10 | 0 | 0.4 |
A26 | A26-30-10 | 26 | 11 | 20 | 1 | 0.6 |
A30 | A30-30-10 | 30 | 15 | 25 | 1P | 0.8 |
A40 | A40-30-10 | 40 | 18.6 | 30 | 1P | 0.8 |
A50 | A50-30-11 | 50 | 22 | 40 | 2 | 1.2 |
A63 | A63-30-11 | 63 | 30 | 60 | 0 | 1.2 |
A75 | A75-30-11 | 75 | 37 | 60 | 0 | 1.2 |
A95 | A95-30-11 | 95 | 45 | 60 | 0 | 2.2 |
A110 | A110-30-11 | 110 | 55 | 75 | 0 | 2.2 |
A145 | A145-30-11 | 145 | 75 | 95 | 0 | 2.2 |
A185 | A185-30-11 | 185 | 90 | 125 | 0 | 3.5 |
A210 | A210-30-11 | 210 | 110 | 150 | 0 | 6.1 |
A260 | A260-30-11 | 260 | 140 | 200 | 0 | 6.5 |
A300 | A300-30-11 | 300 | 160 | 250 | 0 | 6.6 |
Product detail pictures:
Related Product Guide:
How power works in a data center: What you need to know | 220v Contactor Relay
Nokia’s banana phone from The Matrix is back | Lrd12 Overload Relay
Our merchandise are broadly identified and trusted by end users and can satisfy continually developing economic and social requires for Manufacturing Companies for 40a Household Contactor - A line contactor – Simply Buy, The product will supply to all over the world, such as: Barcelona , Canberra , Estonia , Many kinds of different products are available for you to choose, you can do one-stop shopping here. And customized orders are acceptable. Real business is to get win-win situation, if possible, we would like to provide more support for customers. Welcome all nice buyers communicate details of products with us!!
By Elsa from Australia - 2015.02.12 14:52
The company keeps to the operation concept "scientific management, high quality and efficiency primacy, customer supreme", we have always maintained business cooperation. Work with you,we feel easy!
By Annabelle from Brasilia - 2016.07.28 15:46