Protection characteristics
| Item | NO. | Times | the | setting | current | Motion time | Start condition | Ambient temperature | ||
| Three-phase balance motion time | 1 | 1.05 | >2h | Cold state | 20±5℃ | |||||
| 2 | 1.2 | <2h | Heat state | 20±5℃ | ||||||
| 3 | 1.5 | <4min | Cold state | 20±5℃ | ||||||
| 4 | 7.2 | 10A10A | 2s<Tp ≤ 10s ≤ 63A4s<Tp ≤ 10s>63A | Cold stateCold state | 20±5℃20±5℃ | |||||
| Phase-failure motion characteristic | 5 | Any two phases | Another phase | >2h | Cold state | 20±5℃ | ||||
| 1.0 | 0.9 | |||||||||
| 6 | 1.15 | 0 | <2h | Heat state | 20±5℃ | |||||
Selection and ordering dte
| Number Rated current A Fuse links A For contactor | |||
| TA-25 | 0.1~0.160.16~0.25 | 0.50.63 | A9-A40 AL9-AL40 |
|
0.25~0.4 |
1.25 | ||
|
0.4~0.63 |
2 | ||
|
0.63~1 |
4 | ||
| 1~1.41.3~1.8 | 46 | ||
|
1.7~2.4 |
6 | ||
|
2.2~3.1 |
10 | ||
| 2.8~43.5~5 | 1016 | ||
|
4.5~6.5 |
25 | ||
| 6~8.5 | 35 | ||
|
7.5~11 |
35 | ||
| 10~1413~19 | 3550 | ||
|
18~25 |
63 | ||
|
24~32 |
80 | ||