One of Hottest for Main Contacts 3ty7490-0a - Vacuum Interruption VI 12KV WL-39418 – Simply Buy Detail:
A perfect fit for many applications
Load break switches
• Motor contactors
• Circuit breakers
• Reclosers
• Transportation breakers
• Ring main / pad mount units
• Specialized DC applications
• Generator breakers
• Distribution circuit breakers
• Medium voltage switchgear
ELECTRICAL DATA
ELECTRICAL RATINGS(3PHASE) SYMMETRICAL BASIS |
|
1.Rated Voltage |
12KV |
2.Rated Current |
630/1250A |
3.Rated Frequency |
50Hz |
4.Rated Short-time Power Frequency Withstand Voltage(1min) |
42KV |
5.Rated lightring Impulse Withstand Voltage |
75KV |
6. Rated short-circuit breaking current |
25KA |
7. Rated short-circuit making current(peak) |
63KA |
8.Rated operations of short-circuit breaking current interruption |
30times |
9.Rated single capacitor bank breaking current interruption |
630A |
10.Rated Short-time Withstand current |
25KA |
11.Rated peak withstand current |
63KA |
12. Rated Duration of Short-circuit |
4s |
13. Mechanical Life |
20000times |
14.Contact closing force due to bellows and atmosphere |
120±50N |
15.Counterforce at rated contact stroke |
190±60N |
16. Circuit Resistance at Rated Contact Froce Atmosphere Force |
≤20Micro ohms |
17. Shelf Life |
20Years |
18. Contact Erosion Limit |
3mm |
19.Weight of moving parts |
≤1.5kg |
MECHANICAL REQUIREMENTS(REF. VCB) |
|
1. Rated Contact Stroke |
10±1mm |
2.Opening Speed(average) |
1.0±0.25m/Sec |
3.Closing Speed(average) |
0.65±0.15m/Sec |
4.Added contact force |
2000±100N |
5. Maximum Contact Bounse Duration at closing operation |
≤2ms |
6. Contact Bouncing Bank Amplitude of Opeing Operation |
≤2mm |
7.Three-pole simultaneity |
≤1ms |
Mechanical Data Required For Matched Vacuum Switchgear
Main Technical Specification |
Unit |
Specification |
Rated contact stroke |
mm |
9±1 |
Average opening speed |
m/s |
1.0±0.25 |
Average closing speed |
m/s |
0.65±0.15 |
Added contact force |
N |
900/1300/1600±100 |
Contact bouncing duration at closing operation |
ms |
≤2 |
Contact bouncing bank amplitude of opening operation |
mm |
≤2 |
Three-pole simultaneity |
ms |
≤1 |
Product detail pictures:
Related Product Guide:
Microsoft and Razer are working on Xbox keyboard and mouse support | 220v Contactor Relay
How to Fix a Broken Air Conditioner | 220v Contactor Relay
Our business sticks for the basic principle of "Quality could be the life with the firm, and track record will be the soul of it" for One of Hottest for Main Contacts 3ty7490-0a - Vacuum Interruption VI 12KV WL-39418 – Simply Buy, The product will supply to all over the world, such as: America , Chicago , panama , Our solutions have national accreditation requirements for qualified, good quality items, affordable value, was welcomed by individuals all over the world. Our goods will continue to improve inside the order and appear forward to cooperation with you, Really should any of those items be of interest to you, please letus know. We will be satisfied to provide you a quotation up on receipt of the detailed needs.
By Althea from Kenya - 2016.04.28 15:45
Goods just received, we are very satisfied, a very good supplier, hope to make persistent efforts to do better.
By Alexia from India - 2016.12.31 14:53