New Delivery for Contactor Termianl - Vacuum Interruption VI 12KV WL-39418 – Simply Buy Detail:
A perfect fit for many applications
Load break switches
• Motor contactors
• Circuit breakers
• Reclosers
• Transportation breakers
• Ring main / pad mount units
• Specialized DC applications
• Generator breakers
• Distribution circuit breakers
• Medium voltage switchgear
ELECTRICAL DATA
|
ELECTRICAL RATINGS(3PHASE) SYMMETRICAL BASIS |
|
|
1.Rated Voltage |
12KV |
|
2.Rated Current |
630/1250A |
|
3.Rated Frequency |
50Hz |
|
4.Rated Short-time Power Frequency Withstand Voltage(1min) |
42KV |
|
5.Rated lightring Impulse Withstand Voltage |
75KV |
|
6. Rated short-circuit breaking current |
25KA |
|
7. Rated short-circuit making current(peak) |
63KA |
|
8.Rated operations of short-circuit breaking current interruption |
30times |
|
9.Rated single capacitor bank breaking current interruption |
630A |
|
10.Rated Short-time Withstand current |
25KA |
|
11.Rated peak withstand current |
63KA |
|
12. Rated Duration of Short-circuit |
4s |
|
13. Mechanical Life |
20000times |
|
14.Contact closing force due to bellows and atmosphere |
120±50N |
|
15.Counterforce at rated contact stroke |
190±60N |
|
16. Circuit Resistance at Rated Contact Froce Atmosphere Force |
≤20Micro ohms |
|
17. Shelf Life |
20Years |
|
18. Contact Erosion Limit |
3mm |
|
19.Weight of moving parts |
≤1.5kg |
|
MECHANICAL REQUIREMENTS(REF. VCB) |
|
|
1. Rated Contact Stroke |
10±1mm |
|
2.Opening Speed(average) |
1.0±0.25m/Sec |
|
3.Closing Speed(average) |
0.65±0.15m/Sec |
|
4.Added contact force |
2000±100N |
|
5. Maximum Contact Bounse Duration at closing operation |
≤2ms |
|
6. Contact Bouncing Bank Amplitude of Opeing Operation |
≤2mm |
|
7.Three-pole simultaneity |
≤1ms |
Mechanical Data Required For Matched Vacuum Switchgear
|
Main Technical Specification |
Unit |
Specification |
|
Rated contact stroke |
mm |
9±1 |
|
Average opening speed |
m/s |
1.0±0.25 |
|
Average closing speed |
m/s |
0.65±0.15 |
|
Added contact force |
N |
900/1300/1600±100 |
|
Contact bouncing duration at closing operation |
ms |
≤2 |
|
Contact bouncing bank amplitude of opening operation |
mm |
≤2 |
|
Three-pole simultaneity |
ms |
≤1 |
Product detail pictures:



Related Product Guide:
A Short Guide to Vintage Traynor Amps | Circuit Breaker Parts
Larson Electronics LLC Releases Portable 75 KVA Power Distribution Station with 2 520R-GFCI Receptacles | Lrd12 Overload Relay
Always customer-oriented, and it's our ultimate goal to get not only by far the most reputable, trustable and honest supplier, but also the partner for our customers for New Delivery for Contactor Termianl - Vacuum Interruption VI 12KV WL-39418 – Simply Buy, The product will supply to all over the world, such as: New Delhi , Hungary , Turkey , During in 11 years,We have participated in more than 20 exhibitions,obtains the highest praise from each customer. Our company always aim to provide the customer best products with lowest price. We are making great efforts to achieve this win-win situation and sincerely welcome you to join us. Join us, show your beauty. We will always be your first choice. Trust us, you will never lose heart.
The enterprise has a strong capital and competitive power, product is sufficient, reliable, so we have no worries on cooperating with them.
-
Ordinary Discount 3 Poles 24v Contactor - ZL26...
-
Factory For Transit Starter Motor - Motor circ...
-
2017 High quality Power Contactor - EH contact...
-
18 Years Factory Nikko Starting Motor 600-813-9...
-
Good Quality 3 Pole Dc Contactor - Motor circu...
-
Short Lead Time for Ac Telemecanique Contactor ...