Good quality Ac Lighting Contactor - Vacuum Interruption VI 12KV WL-39418 – Simply Buy Detail:
A perfect fit for many applications
Load break switches
• Motor contactors
• Circuit breakers
• Reclosers
• Transportation breakers
• Ring main / pad mount units
• Specialized DC applications
• Generator breakers
• Distribution circuit breakers
• Medium voltage switchgear
ELECTRICAL DATA
|
ELECTRICAL RATINGS(3PHASE) SYMMETRICAL BASIS |
|
|
1.Rated Voltage |
12KV |
|
2.Rated Current |
630/1250A |
|
3.Rated Frequency |
50Hz |
|
4.Rated Short-time Power Frequency Withstand Voltage(1min) |
42KV |
|
5.Rated lightring Impulse Withstand Voltage |
75KV |
|
6. Rated short-circuit breaking current |
25KA |
|
7. Rated short-circuit making current(peak) |
63KA |
|
8.Rated operations of short-circuit breaking current interruption |
30times |
|
9.Rated single capacitor bank breaking current interruption |
630A |
|
10.Rated Short-time Withstand current |
25KA |
|
11.Rated peak withstand current |
63KA |
|
12. Rated Duration of Short-circuit |
4s |
|
13. Mechanical Life |
20000times |
|
14.Contact closing force due to bellows and atmosphere |
120±50N |
|
15.Counterforce at rated contact stroke |
190±60N |
|
16. Circuit Resistance at Rated Contact Froce Atmosphere Force |
≤20Micro ohms |
|
17. Shelf Life |
20Years |
|
18. Contact Erosion Limit |
3mm |
|
19.Weight of moving parts |
≤1.5kg |
|
MECHANICAL REQUIREMENTS(REF. VCB) |
|
|
1. Rated Contact Stroke |
10±1mm |
|
2.Opening Speed(average) |
1.0±0.25m/Sec |
|
3.Closing Speed(average) |
0.65±0.15m/Sec |
|
4.Added contact force |
2000±100N |
|
5. Maximum Contact Bounse Duration at closing operation |
≤2ms |
|
6. Contact Bouncing Bank Amplitude of Opeing Operation |
≤2mm |
|
7.Three-pole simultaneity |
≤1ms |
Mechanical Data Required For Matched Vacuum Switchgear
|
Main Technical Specification |
Unit |
Specification |
|
Rated contact stroke |
mm |
9±1 |
|
Average opening speed |
m/s |
1.0±0.25 |
|
Average closing speed |
m/s |
0.65±0.15 |
|
Added contact force |
N |
900/1300/1600±100 |
|
Contact bouncing duration at closing operation |
ms |
≤2 |
|
Contact bouncing bank amplitude of opening operation |
mm |
≤2 |
|
Three-pole simultaneity |
ms |
≤1 |
Product detail pictures:



Related Product Guide:
Heavy Lift Electromagnet from Microwave Oven Transformers | 25 Amp Circuit Breaker
Xiaomi’s Redmi Note 4 has a big 4,100 mAh battery and a tiny price tag | Lrd12 Overload Relay
Our commission is to serve our users and clients with best quality and competitive portable digital products for Good quality Ac Lighting Contactor - Vacuum Interruption VI 12KV WL-39418 – Simply Buy, The product will supply to all over the world, such as: Moscow , Georgia , Madrid , We will continue to devote ourselves to market & product development and build a well-knit service to our customer to create a more prosperous future. Please contact us today to find out how we can work together.
Managers are visionary, they have the idea of "mutual benefits, continuous improvement and innovation", we have a pleasant conversation and Cooperation.
-
100% Original Factory Lc1-d80 Ac Contactor - S...
-
Factory source Connecting Electric Capacitor - ...
-
factory Outlets for Schneider Contactor Lc1d12m...
-
factory Outlets for Capacitor Switching Contact...
-
Manufactur standard La5fh431 Schneider Electric...
-
New Arrival China Contactor Telemecanique Type ...