Factory making Electric Jib Crane - Vacuum Interruption VI 12KV WL-39418 – Simply Buy Detail:
A perfect fit for many applications
Load break switches
• Motor contactors
• Circuit breakers
• Reclosers
• Transportation breakers
• Ring main / pad mount units
• Specialized DC applications
• Generator breakers
• Distribution circuit breakers
• Medium voltage switchgear
ELECTRICAL DATA
|
ELECTRICAL RATINGS(3PHASE) SYMMETRICAL BASIS |
|
|
1.Rated Voltage |
12KV |
|
2.Rated Current |
630/1250A |
|
3.Rated Frequency |
50Hz |
|
4.Rated Short-time Power Frequency Withstand Voltage(1min) |
42KV |
|
5.Rated lightring Impulse Withstand Voltage |
75KV |
|
6. Rated short-circuit breaking current |
25KA |
|
7. Rated short-circuit making current(peak) |
63KA |
|
8.Rated operations of short-circuit breaking current interruption |
30times |
|
9.Rated single capacitor bank breaking current interruption |
630A |
|
10.Rated Short-time Withstand current |
25KA |
|
11.Rated peak withstand current |
63KA |
|
12. Rated Duration of Short-circuit |
4s |
|
13. Mechanical Life |
20000times |
|
14.Contact closing force due to bellows and atmosphere |
120±50N |
|
15.Counterforce at rated contact stroke |
190±60N |
|
16. Circuit Resistance at Rated Contact Froce Atmosphere Force |
≤20Micro ohms |
|
17. Shelf Life |
20Years |
|
18. Contact Erosion Limit |
3mm |
|
19.Weight of moving parts |
≤1.5kg |
|
MECHANICAL REQUIREMENTS(REF. VCB) |
|
|
1. Rated Contact Stroke |
10±1mm |
|
2.Opening Speed(average) |
1.0±0.25m/Sec |
|
3.Closing Speed(average) |
0.65±0.15m/Sec |
|
4.Added contact force |
2000±100N |
|
5. Maximum Contact Bounse Duration at closing operation |
≤2ms |
|
6. Contact Bouncing Bank Amplitude of Opeing Operation |
≤2mm |
|
7.Three-pole simultaneity |
≤1ms |
Mechanical Data Required For Matched Vacuum Switchgear
|
Main Technical Specification |
Unit |
Specification |
|
Rated contact stroke |
mm |
9±1 |
|
Average opening speed |
m/s |
1.0±0.25 |
|
Average closing speed |
m/s |
0.65±0.15 |
|
Added contact force |
N |
900/1300/1600±100 |
|
Contact bouncing duration at closing operation |
ms |
≤2 |
|
Contact bouncing bank amplitude of opening operation |
mm |
≤2 |
|
Three-pole simultaneity |
ms |
≤1 |
Product detail pictures:



Related Product Guide:
Resident Evil 2 Remake releases January 25th: watch the first trailer | 220v Contactor Relay
Google reportedly paid Andy Rubin $90 million after he allegedly coerced sex from employee | 220v Contactor Relay
We persist with the principle of "quality 1st, assistance initially, continual improvement and innovation to meet the customers" for your management and "zero defect, zero complaints" as the standard objective. To great our service, we present the products and solutions while using the very good top quality at the reasonable cost for Factory making Electric Jib Crane - Vacuum Interruption VI 12KV WL-39418 – Simply Buy, The product will supply to all over the world, such as: New Delhi , Swedish , Macedonia , We guarantee that our company will try our best to reduce customer purchase cost , shorten the period of purchase , stable merchandise quality , increase customers' satisfaction and achieve win-win situation .
Sales manager is very enthusiastic and professional, gave us a great concessions and product quality is very good,thank you very much!
-
Best-Selling For Renault V.i. Starter Motor - ...
-
Wholesale Discount Dc Vacuum Contactor - Nofue...
-
100% Original Factory 48vdc Magnetic Contactor ...
-
Manufacturing Companies for Electric 1p 25a 2no...
-
OEM Factory for Stainless Steel Spring - LA5FF...
-
Factory Supply Light Duty Mini Gantry Crane - ...