ELECTRICAL DATA
|
ELECTRICAL RATINGS(3PHASE) SYMMETRICAL BASIS |
|
|
1.Rated Voltage |
12KV |
|
2.Rated Current |
630/1250A |
|
3.Rated Frequency |
50Hz |
|
4.Rated Short-time Power Frequency Withstand Voltage(1min) |
42KV |
|
5.Rated lightring Impulse Withstand Voltage |
75KV |
|
6. Rated short-circuit breaking current |
25KA |
|
7. Rated short-circuit making current(peak) |
63KA |
|
8.Rated operations of short-circuit breaking current interruption |
30times |
|
9.Rated single capacitor bank breaking current interruption |
630A |
|
10.Rated Short-time Withstand current |
25KA |
|
11.Rated peak withstand current |
63KA |
|
12. Rated Duration of Short-circuit |
4s |
|
13. Mechanical Life |
20000times |
|
14.Contact closing force due to bellows and atmosphere |
120±50N |
|
15.Counterforce at rated contact stroke |
190±60N |
|
16. Circuit Resistance at Rated Contact Froce Atmosphere Force |
≤20Micro ohms |
|
17. Shelf Life |
20Years |
|
18. Contact Erosion Limit |
3mm |
|
19.Weight of moving parts |
≤1.5kg |
|
MECHANICAL REQUIREMENTS(REF. VCB) |
|
|
1. Rated Contact Stroke |
10±1mm |
|
2.Opening Speed(average) |
1.0±0.25m/Sec |
|
3.Closing Speed(average) |
0.65±0.15m/Sec |
|
4.Added contact force |
2000±100N |
|
5. Maximum Contact Bounse Duration at closing operation |
≤2ms |
|
6. Contact Bouncing Bank Amplitude of Opeing Operation |
≤2mm |
|
7.Three-pole simultaneity |
≤1ms |
Mechanical Data Required For Matched Vacuum Switchgear
|
Main Technical Specification |
Unit |
Specification |
|
Rated contact stroke |
mm |
9±1 |
|
Average opening speed |
m/s |
1.0±0.25 |
|
Average closing speed |
m/s |
0.65±0.15 |
|
Added contact force |
N |
900/1300/1600±100 |
|
Contact bouncing duration at closing operation |
ms |
≤2 |
|
Contact bouncing bank amplitude of opening operation |
mm |
≤2 |
|
Three-pole simultaneity |
ms |
≤1 |
Product detail pictures:



Related Product Guide:
Power goes out when pc turns on – Components | Lrd12 Overload Relay
Senate committee cancels votes on judicial nominees after Jeff Flake’s Mueller ultimatum | Lrd12 Overload Relay
We thinks what customers think, the urgency of urgency to act during the interests of a purchaser position of theory, allowing for much better good quality, lower processing costs, prices are extra reasonable, won the new and old buyers the support and affirmation for Factory making Electric Jib Crane - Vacuum Interruption VI 12KV WL-39418 – Simply Buy, The product will supply to all over the world, such as: Uruguay , Macedonia , Auckland , Since its foundation , the company keeps living up to the belief of "honest selling , best quality , people-orientation and benefits to customers. " We're doing everything to supply our customers with best services and best solutions . We promise that we are going to be responsible all the way to the end once our services begin.
The customer service staff's answer is very meticulous, the most important is that the product quality is very good, and packaged carefully, shipped quickly!
-
Hot sale Auxilary Contactor - NB1 2Pole din ra...
-
Chinese wholesale Contactor / Relays - A40-30-...
-
Chinese Professional 40 Amp Mcb Electrical - A...
-
Ordinary Discount 3 Poles 24v Contactor - ZL26...
-
Factory Free sample 160a Disconnect Contacts Dc...
-
18 Years Factory Plastic Lampshades Cover Makin...