China OEM Cage Type Off Circuit Tap-switch - Vacuum Interruption VI 12KV WL-39418 – Simply Buy Detail:
A perfect fit for many applications
Load break switches
• Motor contactors
• Circuit breakers
• Reclosers
• Transportation breakers
• Ring main / pad mount units
• Specialized DC applications
• Generator breakers
• Distribution circuit breakers
• Medium voltage switchgear
ELECTRICAL DATA
|
ELECTRICAL RATINGS(3PHASE) SYMMETRICAL BASIS |
|
|
1.Rated Voltage |
12KV |
|
2.Rated Current |
630/1250A |
|
3.Rated Frequency |
50Hz |
|
4.Rated Short-time Power Frequency Withstand Voltage(1min) |
42KV |
|
5.Rated lightring Impulse Withstand Voltage |
75KV |
|
6. Rated short-circuit breaking current |
25KA |
|
7. Rated short-circuit making current(peak) |
63KA |
|
8.Rated operations of short-circuit breaking current interruption |
30times |
|
9.Rated single capacitor bank breaking current interruption |
630A |
|
10.Rated Short-time Withstand current |
25KA |
|
11.Rated peak withstand current |
63KA |
|
12. Rated Duration of Short-circuit |
4s |
|
13. Mechanical Life |
20000times |
|
14.Contact closing force due to bellows and atmosphere |
120±50N |
|
15.Counterforce at rated contact stroke |
190±60N |
|
16. Circuit Resistance at Rated Contact Froce Atmosphere Force |
≤20Micro ohms |
|
17. Shelf Life |
20Years |
|
18. Contact Erosion Limit |
3mm |
|
19.Weight of moving parts |
≤1.5kg |
|
MECHANICAL REQUIREMENTS(REF. VCB) |
|
|
1. Rated Contact Stroke |
10±1mm |
|
2.Opening Speed(average) |
1.0±0.25m/Sec |
|
3.Closing Speed(average) |
0.65±0.15m/Sec |
|
4.Added contact force |
2000±100N |
|
5. Maximum Contact Bounse Duration at closing operation |
≤2ms |
|
6. Contact Bouncing Bank Amplitude of Opeing Operation |
≤2mm |
|
7.Three-pole simultaneity |
≤1ms |
Mechanical Data Required For Matched Vacuum Switchgear
|
Main Technical Specification |
Unit |
Specification |
|
Rated contact stroke |
mm |
9±1 |
|
Average opening speed |
m/s |
1.0±0.25 |
|
Average closing speed |
m/s |
0.65±0.15 |
|
Added contact force |
N |
900/1300/1600±100 |
|
Contact bouncing duration at closing operation |
ms |
≤2 |
|
Contact bouncing bank amplitude of opening operation |
mm |
≤2 |
|
Three-pole simultaneity |
ms |
≤1 |
Product detail pictures:



Related Product Guide:
Constellation Performance Centaur II 500 power amplifier | Lrd12 Overload Relay
Ameriprise Finl Com (AMP) Shareholder Fdx Advisors Has Increased Stake by $342,804; Fukoku Mutual Life Insurance Company Stake in Amazon Com (AMZN) Raised as Share Price Declined | 25 Amp Circuit Breaker
Our eternal pursuits are the attitude of "regard the market, regard the custom, regard the science" plus the theory of "quality the basic, have faith in the main and management the advanced" for China OEM Cage Type Off Circuit Tap-switch - Vacuum Interruption VI 12KV WL-39418 – Simply Buy, The product will supply to all over the world, such as: Porto , Denver , Ghana , We firmly think that we have the full capability to give you contented merchandise. Wish to collect concerns within you and build a new long-term synergy romantic relationship. We all significantly promise:Csame excellent, better selling price; exact selling price, better quality.
The customer service staff is very patient and has a positive and progressive attitude to our interest, so that we can have a comprehensive understanding of the product and finally we reached an agreement, thanks!
-
Trending Products Street Light Time Switch - M...
-
Manufacturing Companies for Programmable Electr...
-
18 Years Factory Contactless Contactor - ZL75 ...
-
Factory supplied Spare Part Starter Motor - 3U...
-
Hot sale 3 Phase Contactor Relay - 3UA overloa...
-
OEM manufacturer Contactor Components - Motor ...